Permit Number: T20CM08604
Parcel: Unknown

Address:
5443 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM08604
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2021 JPEELDA1 FIRE REVIEW Reqs Change Plans shall include a Code Section and reference the following:
Type of occupancy
Occupant Load
Does the building have fire sprinklers
Does the building have a fire alarm
Type of building construction
Deferred submittals ie: fire sprinkler, fire alarm, kitchen fire suppression system or as necessary.
01/05/2021 JGARCIA1 ZONING REVIEW Passed
12/09/2020 DTRAMME1 ENGINEERING REVIEW Passed
12/10/2020 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/17/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Approved
12/17/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
12/17/2020 PIMA COUNTY WATER REVIEW Completed
12/17/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide a Code review on sheet TS1.
2. Provide a scope of work on sheet TS1.
3. Show hood clearances will be achieved or how the walls and ceiling will be fire-rated to comply with 2018 IMC 507.2.6.
12/17/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Completed