Permit Number: T20CM08572
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM08572
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The previous plan review comment was not addressed.
2. The original submitted plan shows a new branch circuit run to a existing sign via a new 200 amp pedestal with utility conductors installed underground. The submitted revised plan shows 10 #10 conductors in 1-1/4' conduit run to a new sign via a new pole mounted 125 amp service fed overhead.
3. Per the currently adopted 2018 IBC amendments section 112.1.1, the service conductors to the new service must be installed underground. An appeal for a underground service waiver can be submitted for a variance to this code if desired.
4. Provide a complete electrical line diagram, include;
(a) Available fault current and AIC rating of the electrical equipment.
(b) All conduit and conductor sizes and types.
(c) Complete panel schedule with amp ratings of all OCPD's.
(d) Load calculations.
(e) Voltage and phase.
(f) Provide a grounding detail.
5. How are the branch circuits terminating at the sign?
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.