Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW - COMMERCIAL
Permit Number - T20CM08555
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2021 | ARUIZ1 | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Completed | |
| 03/11/2021 | ARUIZ1 | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Completed | |
| 12/08/2020 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 12/08/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Section Manager PROJECT: T20CM08555 – Building Plan 1st Review 3138 E Prince New Multifamily TRANSMITTAL DATE: December 8, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Development Package DP20-0158 must be approved prior to approval of the building plans. 3. Until the building plans are approved by all other review agencies Zoning cannot approve the plans. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 12/08/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide the civil drawings showing the installation of the water service to the buildings as noted in keynote 1, sheet P1.2. Development plans (i.e. the three sheets shown "FOR REFERENCE ONLY") are not for construction. They are also not the current development drawings: for example, the current development plans call for backwater valves for all of the buildings. 2. Clarify the size of the proposed water meter. The development plans call for a 2" meter while the plumbing plans call for a 1-1/2" meter. 3. Show the location of the reduced pressure backflow prevention assembly. Reduced pressure backflow prevention assemblies are required at the water meter for apartment buildings that have common laundry facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 12/08/2020 | JGARCIA1 | ADA | REVIEW | Passed | |
| 12/08/2020 | SSHIELD1 | ZONING HC | REVIEW | Passed | |
| 12/11/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | The Development Package must be approved first. |
| 12/22/2020 | JPEELDA1 | FIRE | REVIEW | Approved | Main drive is 209' exceeds the 2018IFC but approved by Glenn D'Auria on the DP. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/11/2021 | ARUIZ1 | OUT TO CUSTOMER | Completed |