Permit Number: T20CM08548
Parcel: 136342990

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM08548
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM08548
Residential Addition
January 11. 2021
The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed. 1. Please resubmit the plans conforming to the requirements of the residential plot plan found at the following link: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf a. Please add the lot coverage calculations, which include all structures and vehicular use areas on the property.
B. Submit a floor plan so zoning can calculate parking. For any single family dwelling in the R-1 zone with five bedrooms, three parking spaces are required. Please send a floor plan so zoning can confirm.
C. Please ensure all structures are accounted for on the site plan. There appears to be a small unpermitted structure in the southeast corner of the lot that is very close to the property line. If that structure is no longer present, or being removed, please add a note to your plan. If the structure is going to remain, it needs to be permitted, meeting setbacks. Otherwise, the neighbors to the south and east can sign a waiver stating the structure can remain. If the applicant opts for the neighbor waiver, please put the following on the site plan with the neighbor signature: "My Name is __________________ and I am the owner of the property located at ________________________. I have reviewed the site plan and I have no objection to structure being located or constructed ______ feet from the property line as depicted on the site plan. Signature: _____________________________ Date: _________________________________"
If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
01/12/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a complete plan set showing 2018 IRC compliance including a wall and foundation detail showing materials, locations, sizing and fastening.

Provide a floor plan showing all door and window openings to the dwelling.

An exterior door requires a lighted landing area.

Update the wall section. Frame walls require 6" clearance above grade, treated sills, anchored with 1/2" x 10' bolts to a 12" D x 12" W footer with #4 continuous rebar.

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
12/22/2020 ANDREW CONNOR NPPO REVIEW Passed
12/23/2020 SBLOOD1 ENGINEERING REVIEW Passed