Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM08539
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2021 | ANDREW CONNOR | NPPO | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL 4.1 Identification and Descriptive Data All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The Development Package will may be needed and should contain the following identification in the lower right corner of each sheet: Any other relevant case number for reviews or modifications that affect the site. Add case number(s) on each sheet. APPLICABILITY The standards in this Section 7.6.4.B apply to all developments that provide more than four parking spaces. Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-10.0.0, Landscape Plan Requirements. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval. Additional comments may apply |
| 01/12/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T20CM08539 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL COMMENTS: 1. A dwelling unit providing complete independent living facilities requires compliance with design ordinances for handicap, solar water, photo-voltaic and gray water preparations. Design Ordinances adopted by the City of Tucson. 2. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½”control conduit and two ¾” copper piping for water with rooftop termination; straight 3” capped sleeve; or an accessible attic (clear path 30” wide x 30” high) over the water heater. Show appropriate notation. 3. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 . a. Show a minimum 300 SF clear solar-ready zone on a roof or framing plan, T103.3. Model plans should show four typical south facing roof surfaces. b. Label a double breaker space for future Photo Voltaic on the panel schedule opposite end from the main/supply side, T103.9. 4. When the clothes washer is not near an exterior wall show a gray water bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. See details at https://www.tucsonaz.gov/files/pdsd/codes-ordinances/Grey_Water_Options_FINAL_.pdf SITE PLAN: 1. Indicate the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to each dwelling, R106.1.1. Show the point of connection of proposed lines to the utility service for verifying correct sizes and necessary upgrades. FLOOR PLANS: 1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include all threshold conditions for a route from the exterior into the living space. SECTIONS - DETAILS: 1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. Update detail #1/S-3. PLUMBING PLANS: 1. Show hot water pipe with minimum R-3 insulation, N1103.4.2. Show compliance with the maximum length of hot water piping shall not exceed 50’, IPC607.2. MECHANICAL PLANS: 1. Update the whole-house mechanical ventilation description, R303.4; N1103.6 & M1505.4. Show the ZB80 exhaust fan with an appropriate flow rate setting on the plans. A two or three bedroom dwelling of 1501 – 3000 SF requires a 60 CFM continuous setting. 2. Clarify if the attic space is vented or unvented, R806.4. The last note on Sheet M-1 states “unvented”; although Sheet A-5 has a vent calculation and Sheet A-6 has the vent located on the elevation. ELECTRICAL PLANS: 1. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans. 2. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5. 3. Specify high-efficacy lamps for at least 90% of all lighting fixtures, N1104.1. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 01/20/2021 | NMARTEL1 | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL Nicholas Martell, Planner T20CM08539 Duplex and SFR January 20, 2021 The plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed. 1.The duplex and SFR plans require a Development Package. With four proposed dwelling units, this is considered a commercial property. a. For submittal requirements for a Development Package, go to: https://www.tucsonaz.gov/files/pdsd/forms/Submittal_Requirements.pdf b. The application for the Development Package can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pdf Required Changes: Submittal of Development Package If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov |
| 02/05/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | Development Package required. |