Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM08508
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. The previous electrical plan review comment was not addressed. Provide plans sealed by a Engineer registered in the state of Arizona. Also recheck electrical calculations. For example, the 8o amp PV circuit breaker exceeds the allowable per NEC art 705.12B(2). Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
| 07/06/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |