| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a site plan showing the location of the existing and new electrical services. 2. Indicate detailed information describing the scope of work. What are the multi-meter packs replacing? Is this a like for like replacement? 3. Show a electrical line diagram with all the ratings.. Include subpanels, feeder conduit and conductor sizes and types if applicable. 4. If the electrical service ratings in amps is increasing, provide load calculations. 5. Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304 If the upgrade is like for like, please disregard the above statement. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |