Permit Number: T20CM08452
Parcel: 105131100

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM08452
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 ANDREW CONNOR NPPO REVIEW Passed
01/21/2021 EHAMBLI1 ENGINEERING REVIEW Passed
01/21/2021 ELISA HAMBLIN ZONING REVIEW Reqs Change FROM: Elisa Hamblin, AICP
PDSD Zoning Review

PROJECT: T20CM08452; Shipping container storage
Building Plans (1st Review)
364 E Calle Arizona – R-2 Zone

TRANSMITTAL DATE: January 21, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review comments were addressed.

1. Provide a plot plan that meets minimum standards. An example plot plan with instructions can be found online: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf
2. Provide dimensioned elevations for all proposed structures on site to determine appropriate setbacks.
If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: revised building plans
12/07/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM08452
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location and size of buildings and utility meters electric lines from property line to building, R106.1.1. Show the point of connection of proposed lines to the utility service for verifying correct sizes and necessary upgrades.

ELECTRICAL PLANS:

1. Show a single feeder or branch circuit to the accessory (detached) building, NEC 225.30.
2. Show the number and location of receptacle outlets on a floor plan, E3702.2.
3. Show the number and location of switches and lighting fixtures on a floor plan, E3702.2.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review