10/28/2021 STANTEC 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T20CM08395 REV1

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

ARCHITECTURAL COMMENTS
There are no comments.

STRUCTURAL COMMENTS
There are no comments.

MECHANICAL COMMENTS
There are no comments.

PLUMBING COMMENTS
There are no comments.

ELECTRICAL COMMENTS
Sheets 3e6.0 and 3e7.0
1. Panel ā€œGā€ has been added to Sheet 3e7.0, however this panel has not been shown on the one-line diagram on Sheet 3e6.0. {The panel indicates that it derives from Panel SLB1 but there is no Panel G stemming from Panel SLB1. Also, there is no load scheduled for this panel so is it even being installed at this time?}