Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T20CM08395
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2021 | STANTEC | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T20CM08395 REV1 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. ARCHITECTURAL COMMENTS There are no comments. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheets 3e6.0 and 3e7.0 1. Panel āGā has been added to Sheet 3e7.0, however this panel has not been shown on the one-line diagram on Sheet 3e6.0. {The panel indicates that it derives from Panel SLB1 but there is no Panel G stemming from Panel SLB1. Also, there is no load scheduled for this panel so is it even being installed at this time?} |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/28/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |