Permit Number: T20CM08394
Parcel: 14002010A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T20CM08394
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2021 STANTEC 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T20CM08394 REV1

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

ARCHITECTURAL COMMENTS
Sheet 0x1.3
1. This sheet has been modified to show new locations for 4 charging stations placed to one side of each of 4 light pole locations, believed to be serving back-to-back charging stations; however, Sheet 5e0.3 shows 12 new charging station locations, believed to be serving parking spaces back-to-back, and placed on both sides of each of the parking lot poles. Please coordinate. Also, it looks as if these charging stations are currently not entirely developed; there are empty conduits and pedestals only. Please clarify on the plans.
Sheets 0x1.8, 0x1.9, 0x1.10
1. The gates have had added notes indicating “power conduit to office building, see electrical site plan; however, there is no electrical information in the revised drawings or the approved building set regarding electrical for these gates. Please coordinate.
Sheet 5a8.0
1. Several of the doors have had their hardware numbers changed; please provide a door hardware schedule so that the changes can be evaluated.

STRUCTURAL COMMENTS
There are no comments.

MECHANICAL COMMENTS
There are no comments.

PLUMBING COMMENTS
There are no comments.

ELECTRICAL COMMENTS
Sheets 0x1.8, 0x1.9, 0x1.10
1. The gates have had added notes indicating “power conduit to office building, see electrical site plan; however, there is no electrical information in the revised drawings or the approved building set regarding electrical for these gates. Please coordinate.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2021 NGARCIA3 OUT TO CUSTOMER Completed