Permit Number: T20CM08359
Parcel: 121090980

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM08359
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM08359
Residential Addition
January 05, 2021

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.
1. Please submit a detailed floor plan for all structures on the property. For any single family dwelling in the R-1 zone with five bedrooms, three parking spaces are required. For every bedroom over five, one additional space is required for each bedroom. All parking spaces must be located on-site either in a side or rear perimeter yard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. Please submit the floor plan so zoning can determine the amount of spaces required.
2. The side perimeter yard setback on the north side of the property does not meet setbacks. There are two options to address the issue.
a. The applicant may change the plans to reflect a 6' setback to the north property line, or;
b. The applicant may apply for a Design Development Option (DDO) to seek to reduce the required setback. The application for the DDO is found at the following link: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf
If the applicant chooses to apply for the DDO, the following transmittal applies:

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

With a wall height of 7'-2" the applicant is seeking to reduce the side perimeter yard setback from 6' to 5' as measured to the NORTH property line.

A DDO is required.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
01/07/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a single PDF plan set file.

Provide a completed roof framing plan. The LVL ridge beam is undersized. The porch roof requires a support beam.

An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5

Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16
12/01/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/17/2020 ANDREW CONNOR NPPO REVIEW Passed