Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change - IBC Ch. 3. For record purposes, clearly state the the motor vehicle repair garage and storage areas comply with max. allowable quantities of hazardous materials.
- IBC Sect. 406- State compliance with section 406, Motor-vehicle-related occupancies. Especially 406.2 & 406.8.
- IBC Ch. 5. For record purposes, clearly state whether the project is being designed as a Mixed Use 508.3 Nonseparated occupancy or 508.4 Separated occupancy
- In partition details, indicate fastener size and spacing to existing structure at concrete slab & roof.
01/06/2021 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
01/14/2021 ALEXANDRA HINES ZONING REVIEW Approved
01/14/2021 AHINES2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/01/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/01/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatory using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
4. At a minimum, coffee machines and non-carbonated beverage dispensers require the use of a backflow preventer listed to either ASSE 1022, ASSE 1024, or an air gap. Reference: Section 608.17.1.2, IPC 2018.
5. Provide for sterilization and testing of the domestic water system per Section 610.1, IPC 2018.
6. Indirect waste receptors (e.g. detail 6/P2.1) shall not be installed in plenums, crawl spaces, attics, interstitial spaces above ceilings and below floors. Indirect waste receptors shall have ready access. Reference: Section 802.4, IPC 2018.
12/01/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/01/2020 ROBERT SHERRY WATER REVIEW Completed
12/16/2020 JPEELDA1 FIRE REVIEW Approved