Permit Number: T20CM08321
Parcel: 137291990

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM08321
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM08321
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Provide a floor plan showing any door between the dwelling and garage with 20 minute fire rating. Show the type of existing wall separating the dwelling and garage with 20 minute fire rating such as 1/2” sheet rock or any masonry material.

SECTIONS - DETAILS:

1. Show a cross-section detail of each type of new exterior wall, R106.1.1. Show the method of fastening the frame wall at top and base.
2. Show a detail of exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) or 2” clearance above a concrete surface, R602.10.8 & R403.1.6. A concrete foundation stem may be required.

ELECTRICAL PLANS:

1. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5 and E3901.9.
2. Show any lighting and switch locations.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review
11/30/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/15/2020 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM08321
Residential Garage Conversion
December 15, 2020

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. Please resubmit the plans conforming to the requirements of the residential plot plan found at the following link: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf a. A full site plan with all setbacks, elevation drawings, lot coverage calculations and other plot plan standards is required.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
12/17/2020 ANDREW CONNOR NPPO REVIEW Passed