Permit Number: T20CM08306
Parcel: 129052700

Address:
2932 E 18TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM08306
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a complete plan set showing 2018 IRC compliance including post, beam, rafter and foundation location and sizing.

A carport requires a clear 3 foot fire separation distance to the property line unless the structure includes a one-hour rated wall that is placed at the edge of the roof overhang. See IBC Table 721.1(2), Items 15-1.1 to 16-1.3 for a listing of fire rated materials.
11/30/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/15/2020 NMARTEL1 ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Nicholas Martell, Planner


PROJECT: T20CM08306
2932 E 18th St.
Garage Addition

TRANSMITTAL: 12/15/2020

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 8'6", the applicant is requesting a setback reduction from 6' to 1'5" as measured to the EAST property line.

A DDO is required

You may submit your application for a DDO by filling out the application found here:
https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf

If the applicant does not wish to go through the DDO process, they may remove the structure in violation.
12/17/2020 ANDREW CONNOR NPPO REVIEW Passed