Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM08305
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM08305
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/30/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/30/2020 ROBERT SHERRY WATER REVIEW Completed
12/01/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/16/2020 JPEELDA1 FIRE REVIEW Approved
12/17/2020 SAMUEL ROGERS ZONING REVIEW Approved
12/17/2020 SROGERS2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/18/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Add note to the Lighting Plan that "all light fixtures are existing fixtures to be relocated as shown". 2018 IBC 107.2.1.
2. Show relocated exit lights on the Lighting Plan. 2018 IBC 107.2.1.
3. Show emergency lights on the Lighting Plan. 2018 IBC 1008.2.
4. Provide occupancy sensors in locations required by 2018 IECC C405.2.1.
12/18/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change 1. Per telephone conversation with G. Schau all light fixtures are existing and relocated. Please revise the Reflected Ceiling Plan to show the correct line type for all relocated light fixtures per the Symbol Legend on this sheet.
2. The exit lights in the Legend and on the plan are shown as "existing". However, these lights should be shown as "relocated" as they are on new walls.
3. Please provide the keynote "3" that is shown on the plan at exit lights.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2020 PC_CANDERS1 OUT TO CUSTOMER Reqs Change
12/18/2020 PC_CANDERS1 REJECT SHELF Reqs Change
12/18/2020 PC_CANDERS1 APPROVAL SHELF Reqs Change