Permit Number: T20CM08179
Parcel: 124081010

Review Status: Completed

Review Details: OTHER

Permit Number - T20CM08179
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Revise the references to the 2018 IRC to 2017 NEC on the plan.
2. Provide a total electrical load calculation for the SES and indicate riser conductor sizes and types.
3. Are the sub panels being replaced? If so, indicate feeder conduit or cable sizes and types and provide a complete line diagram. Also show or indicate the locations of the sub panels.
4. If the new electrical service is being installed in a different location as the existing, then provide a site plan showing the proposed location.
5. Indicate the total Amp, AIC, Phase, Voltage ratings of the electrical service equipment on the plan. Include the main breaker sizes.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2020 PCAMARE1 OUT TO CUSTOMER Completed