Permit Number: T20CM08135
Parcel: 12709011N

Address:
201 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM08135
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 SSHIELD1 ENGINEERING REVIEW Passed
01/06/2021 STEVE SHIELDS ZONING REVIEW Passed
12/02/2020 JPEELDA1 FIRE REVIEW Approved
12/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a panel and circuit designation including a panel schedule with load calculations. Show panel location and conduit/feeder routing.
2. Provide listing information of the charging equipment. NEC 625.5
3. Provide disconnection means per NEC 625.43
4. Provide plans designed and sealed by an Engineer registered in the State of Arizona. ARS 32-125, R4-30-304. State of Arizona Technical Board of Registration.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
12/15/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/15/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/18/2020 JGARCIA1 OIP REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2021 IMONSHI1 OUT TO CUSTOMER Completed