| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 01/06/2021 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 12/02/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/10/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a panel and circuit designation including a panel schedule with load calculations. Show panel location and conduit/feeder routing. 2. Provide listing information of the charging equipment. NEC 625.5 3. Provide disconnection means per NEC 625.43 4. Provide plans designed and sealed by an Engineer registered in the State of Arizona. ARS 32-125, R4-30-304. State of Arizona Technical Board of Registration. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 12/15/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/15/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/18/2020 | JGARCIA1 | OIP | REVIEW | Passed |