Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM08061
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Revise the 2012 IECC to the current 2018 IECC for the lighting. Do not confuse the IECC with the Outdoor Lighting Code. 2. Indicate conduit, conductor sizes and types for all feeders at the service equipment and branch circuits to lighting. 3. REF; 2012 Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements. Provide lighting plans with the following information on the plans; (a) Provide a complete luminaire schedule. (b) Size of the parcel in acres. (c) See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing. (d) 402.1 (light source color temperature requirements), shielding requirements, etc . (e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1. (f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. (g) Specify any exceptions used. (h) Curfew lighting controls If applicable. Do not confuse the Outdoor Lighting Code with the IECC. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/17/2020 | PCAMARE1 | OUT TO CUSTOMER | Completed |