Permit Number: T20CM08038
Parcel: 11812088B

Address:
1310 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM08038
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2021 SAMUEL ROGERS ZONING REVIEW Approved
11/16/2020 DTRAMME1 ENGINEERING REVIEW Passed
11/25/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1and 2902.5, IBC 2018 and Section 410.3, IPC 2018. (The plans show a code-compliant dual-height drinking fountain but the plumbing fixture schedule specifies a single level drinking fountain.)
3. Revise detail 2/P2 to show the specified vacuum relief valve for the water heater installed per the manufacturer's listing information, i.e. with no valves located between the vacuum relief valve and the water heater. Reference: Sections 303.2 and 504.2, IPC 2018.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
5. Provide a cleanout for the section of 3" horizontal drain located immediately downstream of the drinking fountain. Reference: Section 708.1.1, IPC 2018.
11/25/2020 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
11/25/2020 JVINCEN1 FIRE REVIEW Approved
11/30/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a reference copy of the Landlord's mechanical plans. Reference: Section 107.2.1, IBC 2018.
12/09/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the 2018 IECC for the lighting.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
12/22/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Title Sheet, Architectural Sheets, Structural Sheets, Structural Calculations: Please indicate on the architectural and civil seals the date the seal was signed.
12/22/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed