Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM07948
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2021 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 12/01/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | These comments from the first electrical plan review are satisfied. 12-01-2020. Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E3.1. NEC requires the Rapid Shutdown Label to be installed on the Rapid Shutdown Initiation Device NEC 690.12B2 and part 690.12C… Plan Sheet E3.1, Per identification 3 on ADDITIONAL LABELS, States the Rapid Shutdown Label is to be installed at the MAIN SERVICE DISCONNECT…The PV interconnection is on the supply side of the Main 1000 amp breaker.. Please explain how this will initiate Rapid Shutdown of the PV system in the event the Main Breaker is switched to the off position. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 12/02/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/14/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
| 12/17/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/11/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |