Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The City of Tucson, not Pima County, is the Authority Having Jurisdiction (the first sheet M0.1, Codes and Regulations).
2. The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2018 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2018; for HVAC systems serving multiple zones (e.g. AC1-2), see Section 403.3.1.1.2.3, IMC 2018.
3. Show that the proposed replacement rooftop unit and the proposed split system heat pump unit meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.
4. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.