Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM07867
Parcel: Unknown

Address:
2805 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM07867
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2020 ROBERT SHERRY WATER REVIEW Completed
11/24/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The architectural site plan, A1.1, shows the general location of the water meter and the route of the water service to the building but refers to the plumbing plans for the construction details (e.g. sizes, materials, shut off valve, etc.). Provide the missing information. Reference: Section 107.2.1, IBC 2018.
2. The architectural site plan, A1.1, shows the general location and route of the building sewer but refers to the plumbing plans for the construction details (e.g. sizes, materials, slope, cleanout locations, etc.). Provide the missing information. Reference: Section 107.2.1, IBC 2018.
3. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
4. Provide dimensions of the scuppers and downspouts. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1108, IPC 2018.
11/24/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.
2. Change the COMcheck Mechanical Compliance Certificate from "alteration" to "new construction."
3. Show how one of the "Additional Efficiency Package Options" (C406, IECC 2018) is to be accomplished. Reference: Section C401.2, IECC 2018.
4. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade (e.g. the east side of the rooftop heat pump). Reference: Section 304.11, IMC 2018.
11/25/2020 JVINCEN1 FIRE REVIEW Approved
12/22/2020 STANTEC ELECTRICAL-COMMERCIAL REVIEW Completed
12/22/2020 ARUIZ1 ZONING REVIEW Needs Review
12/22/2020 STANTEC BUILDING-COMMERCIAL REVIEW Completed
12/22/2020 ARUIZ1 ENGINEERING REVIEW Needs Review
12/22/2020 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2020 ARUIZ1 OUT TO CUSTOMER Completed