Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM07863
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/24/2020 | ROBERT SHERRY | WATER | REVIEW | Needs Review | |
| 11/24/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The portion of architectural plans for the suite does not contain enough information to determine if any previous changes to the suite were part of a valid permit. Reference: Sections 107.2.1 and 107.3.2, IBC 2018. 2. The photograph of the kitchen area shows a Type II hood located over a gas-fired range. Heavy-duty appliances such as the range require the installation of a Type I hood equipped with grease filters and a fire suppression system. Installation of a Type I hood will require drawings produced by an Arizona Registrant. Reference: Section 507.2, IMC 2018 and Section 107.1, IBC 2018. |
| 11/24/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/25/2020 | JVINCEN1 | FIRE | REVIEW | Reqs Change | The appliance shown in the picture will require a Type I hood per mechanicals comments. Will require a hood fire suppression system. |
| 12/03/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Per the Mechanical Reviewers Comments. Verify that any changes required to satisfy the mechanical issues will not affect the Electrical requirements or if Electrical modifications are required, please submit a complete electrical plan for review. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 12/16/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/16/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Per the IBC Section 107, construction drawings shall be prepared by a registered design professional. Please provide. 2. General: Please provide a site plan, building plan, and sections/details as required by the IBC Section 107.2. 3. General: Please provide structural calculations to verify the existing roof structure is capable of supporting the hood. Include details on the plans of how the hood is supported at the roof structure. 4. General: Please provide a valuation (labor + materials) for the installation of the hood and ductwork. 5. General: Please provide written responses to all review comments. |
| 12/18/2020 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 12/30/2020 | SAMUEL ROGERS | ZONING | REVIEW | Passed |