Permit Number: T20CM07840
Parcel: 133180630

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM07840
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM07840
PLAN REVIEW COMMENTS
Plan review for the above referenced structure is completed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code, 2018 International Fire Code, 2017 National Electrical Code and Arizona Revised Statutes. All features were checked to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL NOTES:
• Limit all code references to those recognized by the City of Tucson. The 2017 NEC is listed at the Planning & Development Services web site.
• Provide manufacturer specification sheets for collector panels, inverter and mounting hardware.
• Provide compliance with the 2018 International Fire Code 1204.2.1.1 showing a 36” wide access pathway from the eave to the ridge on both sides of the building when the slope is greater than 2:12.
DIAGRAMS / CALCULATIONS
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts.
2. Show a plan of sufficient lag-bolt connections for maintaining the up-lift calculation and with standoff placement for preventing point loads over 45 pounds, R301.1.
3. Show correct Overcurrent Protection Breaker sizes for the connected devices/ratings. Refer to the Pima County PV calculator for determining appropriate sizes at: http://www.pimaxpress.com Under the Building Permitting tab select Forms & Calculators for the Standard or Micro Inverter PV tool.
4. Show the continuous AC grounding electrode conductor size complying with Table 250.66 and not smaller than #8 (copper), NEC 690.47(A). Show this conductor size between the inverter grounding terminal at the combiner panel and the service ground terminal at the service panel.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review