Permit Number: T20CM07828
Parcel: 13225066A

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T20CM07828
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide electrical plans that are sealed by an Electrical Engineer registered in the State of Arizona. ARS 32-125/ R4-30-304.
2. Provide detailed information as to the proposed scope of work and identify the new work from the existing.
3. If there are classified areas per NEC, please identify them on the plans if included in the scope of work.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.