Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T20CM07773
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.) Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. Instructions: Is this for a new or existing activity application? – Please select New Application. Submission Type – Select Floodplain Use Permit. Project Name – Enter a name for your project. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided. Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.) Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account. Complete the Contractor, Owner and Architect/Engineer sections as applicable. Supporting Documentation Upload – Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful. Sign the application and submit. You will be given an activity number for your submittal. Please copy and send this number back to us so we can continue the review. |
| 02/04/2021 | IMONSHI1 | COMMUNICATIONS | REVIEW | Passed | |
| 12/28/2020 | JPEELDA1 | FIRE | REVIEW | Approved | DRAWINGS ARE LOCKED SO A STAMP CANNOT BE APPLIED BUT WE APPROVING THE DRAWINGS. |
| 12/29/2020 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 12/29/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/29/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Please provide structural calculations for the structural adequacy of the existing tower and foundation due to the antenna additions. 2. General: Please provide a project valuation (labor + materials) for this project. |
| 12/29/2020 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/04/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |