Permit Number: T20CM07770
Parcel: 10821328B

Address:
1840 E RIVER RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM07770
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Relocate the smoke detectors upstream of any outside air connections. Reference: Section 606.2.1, IMC 2018. [Initial comment: Provide smoke detection for fan coil units and heat pumps that are sharing a common return air plenum with a combined air handling capacity exceeding 2,000 CFM. Reference: Section 606.2.2, IMC 2018.]
01/14/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the Plumbing Overall Roof Plan if it is still part of the activity. If it is no longer needed, remove it from the sheet index.
2. The revised plans show additional appliances. Appliances (e.g. espresso machines) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
01/25/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/26/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved