Permit Number: T20CM07770
Parcel: 10821328B

Address:
1840 E RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07770
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2020 DTRAMME1 ENGINEERING REVIEW Passed
11/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide specifications for water heater WH-1. Reference: Section 107.2.1, IBC 2018.
11/23/2020 ROBERT SHERRY WATER REVIEW Completed
11/24/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide smoke detection for fan coil units and heat pumps that are sharing a common return air plenum with a combined air handling capacity exceeding 2,000 CFM. Reference: Section 606.2.2, IMC 2018.
2. Show how fan coil FC-2.4 will be supplied with the scheduled 200 CFM of outside air. Reference: Section 403.1, IMC 2018
11/25/2020 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/25/2020 JVINCEN1 FIRE REVIEW Approved
12/03/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide for Tamper Resistant Receptacles where applicable per NEC art 406.12 or 406.2.
2. Designate a Panel for all the electrical devices (receptacles) shown on the power plans.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
12/07/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0: The registered design professional must seal, sign, and date this sheet.
2. Sheet A1.0; Code Analysis Data (Plumbing Fixtures): The water closets indicate one per 15 for the first 50. Please revise per the IBC Table 2902.1.
3. Sheets A2.0, A2.1, and A2.2; Wall Types: Wall Types A and B reference Details 2, 3, and 9/A8.0. Please revise the sheet reference. Should 10/A9.0 be added to that note? Please verify.
4. Sheet A2.2; Third Floor Plan: At the Small Break Room 312, an Enlarged Plan references 2/A5.2. Please verify that plan reference.
5. Sheet A2.3; Enlarged Stair Plan: Sections 2, 3, and 4/A9.0 are indicated on this plan. Please verify these sections are correct.
6. Sheet A4.0; Roof Plan: Keynote 5 was not located on the plan. Please verify.
7. General: Please provide a Special Inspections Certificate with Parts A and B completed.
8. General: Please provide written responses to all review comments.
12/29/2020 STEVE SHIELDS ZONING REVIEW Approved