Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM07770
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/09/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
11/23/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide specifications for water heater WH-1. Reference: Section 107.2.1, IBC 2018. |
11/23/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
11/24/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide smoke detection for fan coil units and heat pumps that are sharing a common return air plenum with a combined air handling capacity exceeding 2,000 CFM. Reference: Section 606.2.2, IMC 2018. 2. Show how fan coil FC-2.4 will be supplied with the scheduled 200 CFM of outside air. Reference: Section 403.1, IMC 2018 |
11/25/2020 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/25/2020 | JVINCEN1 | FIRE | REVIEW | Approved | |
12/03/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide for Tamper Resistant Receptacles where applicable per NEC art 406.12 or 406.2. 2. Designate a Panel for all the electrical devices (receptacles) shown on the power plans. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
12/07/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0: The registered design professional must seal, sign, and date this sheet. 2. Sheet A1.0; Code Analysis Data (Plumbing Fixtures): The water closets indicate one per 15 for the first 50. Please revise per the IBC Table 2902.1. 3. Sheets A2.0, A2.1, and A2.2; Wall Types: Wall Types A and B reference Details 2, 3, and 9/A8.0. Please revise the sheet reference. Should 10/A9.0 be added to that note? Please verify. 4. Sheet A2.2; Third Floor Plan: At the Small Break Room 312, an Enlarged Plan references 2/A5.2. Please verify that plan reference. 5. Sheet A2.3; Enlarged Stair Plan: Sections 2, 3, and 4/A9.0 are indicated on this plan. Please verify these sections are correct. 6. Sheet A4.0; Roof Plan: Keynote 5 was not located on the plan. Please verify. 7. General: Please provide a Special Inspections Certificate with Parts A and B completed. 8. General: Please provide written responses to all review comments. |
12/29/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved |