Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM07762
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2020 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plan set has stamps from other entities. Plan set references old codes. Please adjust plan set dates, stamps and drawing notes. |
| 12/03/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/03/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Per the 2018 IBC Section 107.2.6, the construction documents submitted with an application for a permit shall be accompanied by a site plan meeting the requirements of that Section. Please provide. 2. General: Per the 2018 IBC Section 107.3.4, a registered design professional in responsible charge shall be designated to act in reviewing and coordinating submitted documents prepared by others. The registered design professional in responsible charge must indicate in a sealed, signed, dated letter that he/she has reviewed the submitted documents and they were found to meet the design requirements of the 2018 IBC. 3. General: Please provide written responses to all review comments. |
| 12/08/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 12/18/2020 | JGARCIA1 | OIP | REVIEW | Passed | |
| 12/30/2020 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | DP will need to be approved and issued before the building permit can be issued. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 12/30/2020 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | FROM: Samuel Rogers PDSD Zoning Review Section PROJECT: T20CM07762 (Project Number) Aluminum Awning (1st Review) 3110 N 1st Av TRANSMITTAL DATE: 12/30/20 DUE DATE: 12/10/20 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: All structures proposed on commercial sites must be approved on a Development Package prior to the building permit’s approval. A Development Package must be submitted to permit the aluminum awning. Development Package Application: https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pdf Development Package Submittal checklist: https://www.tucsonaz.gov/files/pdsd/forms/Submittal_Requirements.pdf Presubmittal Application (not required): https://www.tucsonaz.gov/files/pdsd/forms/Thursday_Pre-Submittal_Meeting_Application.pdf If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/04/2021 | PCAMARE1 | OUT TO CUSTOMER | Completed |