Review Details: REVISION - - 1ST
Permit Number - T20CM07743
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Please address the electrical plan review comments and provide a written response 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. 2. Why does the Site plan and line diagrams show the 600 amp electrical service equipment as existing and the Equipment Elevation plan shows new Meter, Main Service Disconnect. Provide a detailed line diagram, I- line and 3-Line, showing all service equipment, grounding, conduits, conductors, and indicate what is new, existing and or relocated existing. 3. Why is there an unfused and a fused AC disconnect in line with each other ahead of the gutter? Also verify the AC fused disconnect is rated as Suitable for Service Equipment and meets the AIC rating for the available fault current per TEP. NEC 690.13(C). Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/06/2022 | VVERA1 | OUT TO CUSTOMER | Completed |