Permit Number: T20CM07743
Parcel: 133290060

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM07743
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2020 SBLOOD1 ENGINEERING REVIEW Passed
11/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide electrical plans sealed by an Engineer registered in the State of Arizona.
2. Provide a grounding detail for the racking and PV Modules including Listed Hardware.
3. Indicate the rating for all the OCPD's in the AC Combiner Box. Is this a Box or a panel? If it's a panel, show the ratings.
4. The labels plan shows the Rapid Shutdown Label applied to what appears to be the Electrical Service Panel. The interconnection is a line side tap..How will the rapid shutdown be initiated at this equipment…See NEC 690.12C.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
12/02/2020 JPEELDA1 FIRE REVIEW Reqs Change Plans shall show the actuall size of the aray's and the lenght. Plans shall show the distance from aray's to the roof edge
Plans shall show the separations required by the fire code
If you have any questions please email me Jennifer.Peel-Davis@TucsonAz.gov
12/03/2020 SAMUEL ROGERS ZONING REVIEW Approved
12/16/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2020 PCAMARE1 OUT TO CUSTOMER Completed