Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM07743
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2020 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 11/10/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide electrical plans sealed by an Engineer registered in the State of Arizona. 2. Provide a grounding detail for the racking and PV Modules including Listed Hardware. 3. Indicate the rating for all the OCPD's in the AC Combiner Box. Is this a Box or a panel? If it's a panel, show the ratings. 4. The labels plan shows the Rapid Shutdown Label applied to what appears to be the Electrical Service Panel. The interconnection is a line side tap..How will the rapid shutdown be initiated at this equipment…See NEC 690.12C. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 12/02/2020 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans shall show the actuall size of the aray's and the lenght. Plans shall show the distance from aray's to the roof edge Plans shall show the separations required by the fire code If you have any questions please email me Jennifer.Peel-Davis@TucsonAz.gov |
| 12/03/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
| 12/16/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/18/2020 | PCAMARE1 | OUT TO CUSTOMER | Completed |