| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 11/19/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/03/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete compliance with the 2012 Outdoor Lighting Code for the exterior lighting. 2. Revise all the references to the IRC to 2017 NEC. Because this is considered a commercial project. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting code |
| 12/03/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/29/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/30/2020 | PCAMARE1 | OUT TO CUSTOMER | Completed |