Permit Number: T20CM07673
Parcel: 131042640

Address:
4901 E 27TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM07673
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/25/2020 NMARTEL1 ZONING REVIEW Approved
11/25/2020 NMARTEL1 NPPO REVIEW Passed
12/09/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM07673
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

STRUCTURAL PLANS:

1. Provide a complete roof framing plan with a beam sized with appropriate load carrying capacity, R301.1. Adding insulation and sheet rock at the ceiling adds loading on an undersized 4x6 beam. Show an appropriate upgrade.

SECTIONS - DETAILS:

1. Show frame wall supported with a foundation stem for achieving the 6” clearance between framing and ground (R317.1 item 5) or show the existing floor level at 6” above grade.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-30 for this size addition.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity. If you have any questions, please contact:

Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review
12/18/2020 SBLOOD1 ENGINEERING REVIEW Passed