Permit Number: T20CM07641
Parcel: 128062770

Address:
6039 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07641
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2020 DTRAMME1 ENGINEERING REVIEW Passed
11/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change A note on sheet A2 calls for "ADDING NEW GREASE TRAP FOR RASPADOS." Clarify the scope of work for this activity. Reference: Section 107.2.1, IBC 2018.
11/23/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/23/2020 ROBERT SHERRY WATER REVIEW Completed
11/25/2020 JVINCEN1 FIRE REVIEW Approved
11/30/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a complete electrical wiring diagram on the electrical plan, include relays, switches, to accommodate the sequence of operation per the Mechanical Exhaust fan and Kitchen Hood equipment schedule notes on plan sheet M1.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
12/09/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/09/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/10/2020 NMARTEL1 ZONING REVIEW Approved