Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM07637
Parcel: 13612833C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07637
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2020 DTRAMME1 ENGINEERING REVIEW Passed
11/19/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
2. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.
11/19/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. What is the purpose of the "Fixture Shop" and why is the area being exhausted? Is there adequate make-up air to offset the exhaust flow rate? Reference: Section 107.2.1, IBC 2018 and Section 501.4, IMC 2018.
2. What are the activities being performed in the MI room? Reference: Section 107.2.1, IBC 2018.
11/19/2020 ROBERT SHERRY WATER REVIEW Completed
12/02/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/02/2020 JPEELDA1 FIRE REVIEW Approved
12/02/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the currently adopted 2018 IECC for the lighting.
Ref; 2018 IECC
12/02/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/22/2020 STEVE SHIELDS ZONING REVIEW Approved