Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM07598
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM07598
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/25/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/02/2020 JPEELDA1 FIRE REVIEW Approved
12/03/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed CORRECTIONS SUBMITTED 12/03/2020
1. Correct the boxed note in detail 2/M2 to comply with Section 506.3.11.2, IMC 2018. Fire wrap "…shall not be installed for the sole purpose of reducing clearances to combustibles at isolated sections of grease duct." The grease duct shall be continuously enclosed from the origination of the grease duct to the termination of the grease duct.
2. Verify that the existing air diffuser located adjacent to the hood is not a 4-way diffuser that will disrupt the hood performance. Reference: Section 304.1, IMC 2018.
3. Identify and show the appliances that will be located under the new hood. Reference: Sections 507.4 and 507.5, IMC 2018.
12/07/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/18/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/22/2020 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2020 PCAMARE1 OUT TO CUSTOMER Completed