Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM07598
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/25/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
12/02/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
12/03/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | CORRECTIONS SUBMITTED 12/03/2020 1. Correct the boxed note in detail 2/M2 to comply with Section 506.3.11.2, IMC 2018. Fire wrap "…shall not be installed for the sole purpose of reducing clearances to combustibles at isolated sections of grease duct." The grease duct shall be continuously enclosed from the origination of the grease duct to the termination of the grease duct. 2. Verify that the existing air diffuser located adjacent to the hood is not a 4-way diffuser that will disrupt the hood performance. Reference: Section 304.1, IMC 2018. 3. Identify and show the appliances that will be located under the new hood. Reference: Sections 507.4 and 507.5, IMC 2018. |
12/07/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/18/2020 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
12/22/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/23/2020 | PCAMARE1 | OUT TO CUSTOMER | Completed |