Permit Number: T20CM07552
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07552
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2020 JPEELDA1 FIRE REVIEW Approved
11/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
11/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide general room exhaust for any cooking appliance (e.g. the waffle cone maker) that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Note that additional exhaust will be required when future cooking appliances are installed. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.
2. Demonstrate energy code compliance for the alterations to the building envelope (e.g. storefront revisions) using calculations based on the current code. Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018.
11/17/2020 ROBERT SHERRY WATER REVIEW Completed
11/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/02/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/02/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/18/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/22/2020 STEVE SHIELDS ZONING REVIEW Approved