Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM07542
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/12/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Correct the last sentence in plumbing keynote #7 (P1) to read: Maximum length from HW loop to fixture shall be24" for ½" piping. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] |
| 01/14/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Could not locate compliance with the 2018 IECC for the lighting as stated in the response letter. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 01/21/2021 | LBOWERS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |