Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T20CM07524
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/15/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Indicate the available fault current at the electrical service equipment, and AIC rating of all the new service equipment and panel. 2. Show service grounding. 3. Provide a complete panel schedule and designate panel identification on the line diagram and floorplan. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/22/2020 | LBOWERS1 | OUT TO CUSTOMER | Completed |
| 12/22/2020 | LBOWERS1 | REJECT SHELF | Completed |