Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM07514
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/12/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 11/23/2020 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 11/23/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheets 3 and 4 of 23; Site Layout Plan: Please indicate where the shade structure (Sheet 20) is located on this plan. 2. Sheet 20 of 23; Shade Structure: Please provide structural calculations for the shade structure and the foundation. 3. Sheet 21 of 23; Radio Antenna: Please provide structural calculations for the radio antenna foundation. 4. General: Please provide written responses to all review comments. |
| 12/07/2020 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 12/07/2020 | STEVE SHIELDS | ZONING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/14/2020 | JGARCIA1 | APPROVAL SHELF | Completed |
| 12/14/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 12/14/2020 | JGARCIA1 | REJECT SHELF | Completed |