Permit Number: T20CM07495
Parcel: 130080780

Address:
3743 E GARDEN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM07495
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM07495

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with code compliance.

Place each plan sheet into a single PDF file for reviewing as a complete plan set.

Use the Residential Plan Requirements & Checklist at https://www.tucsonaz.gov/pdsd/residential-permits

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide a site plan showing all buildings, R106.1.1. Show setback measurements to property lines and location of utility lines to the building.

FLOOR PLAN:

Provide a floor plan showing each room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window opening into the proposed space.

FRAMING PLAN:

Provide a roof framing plan showing beam and rafter location and sizes.

SECTIONS - DETAILS:

Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the foundation dimensions and floor separation from grade with minimum code compliance. New exterior walls require compliant attachment to a foundation with minimum 6" spacing above exterior grade.

ELECTRICAL PLANS:

Provide any wiring details showing code compliant devices and sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior.

OUTDOOR LIGHTING CODE

Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations or show proposed fixtures as Full Cut Off (night sky friendly).

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
03/09/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL
FROM: PDSD Zoning Review
PROJECT: T20CM07495
Slab
3743 E Garden St

TRANSMITTAL DATE: March 9, 2021

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.
1. This comment was not addressed. Provide a residential plot plan that shows the location of the proposed pad that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.
If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.