Permit Number: T20CM07421
Parcel: 133290060

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM07421
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/06/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The revised mechanical plan does not show any air being supplied into the breathing zone of the new prep room (see Breathing Zone definition, Section 202, IMC 2018). [Second comment: Show how ventilation air is to be introduced into the prep room breathing zone using the existing AC-2. Provide sufficient outside air using AC-1 to account for the outside air requirements of the breakroom, office, and transfer air to the restroom (a total of 105 CFM). Show how outside air is to be introduced to the breakroom and office using AC-1. Reference: Sections 403.2.2 and 403.3.1.1, IMC 2018.] [Initial comment: Show how the new dough room is to be ventilated. Reference: Sections 401.2 and 401.3, IMC 2018.]
04/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/16/2021 STEVE SHIELDS ZONING REVIEW Approved