Permit Number: T20CM07421
Parcel: 133290060

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM07421
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 10: Structural calculations were not provided in this submittal.
2. Previous Comment 11: The Special Inspections Certificate with Parts A and B completed was not provided in this submittal.
02/23/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Shower valves to comply with ASSE 1016, not ASSE 1070. [Initial comment: Provide shower valves that comply with the requirements of Section 412.3 and 424.5, IPC 2018.]
2. The maximum pipe length shown in Table C404.5.1, IECC for a lavatory in a public restroom is 24-inches. [Initial comment: Show the location of the water heater serving the new bathroom. If the developed length of the hot water supply piping is greater than the maximum pipe length shown in Table C404.5.1, IECC, 2 feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.]
02/23/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Component descriptions do not correspond to the construction shown on the plans (e.g. no continuous insulation for roof or walls, no exterior walls on the south side of the additions). Coordinate the component descriptions with the construction details. [Initial comment: Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code (e.g. COMcheck). Reference: Sections C103.2, C303, and C502.1, International Energy Conservation Code 2018.]
2. Provide locking access port caps for the condensing units per Section 1101.10, IMC 2018 or locate the condensing unit to a controlled space. [Initial comment: Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018.]
3. Show how ventilation air is to be introduced into the prep room breathing zone using the existing AC-2. Provide sufficient outside air using AC-1 to account for the outside air requirements of the breakroom, office, and transfer air to the restroom (a total of 105 CFM). Show how outside air is to be introduced to the breakroom and office using AC-1. Reference: Sections 403.2.2 and 403.3.1.1, IMC 2018. [Initial comment: Show how the new dough room is to be ventilated. Reference: Sections 401.2 and 401.3, IMC 2018.]
02/25/2021 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

PROJECT: T20CM07421
8321 E Broadway Blvd.
TI Food Service
TRANSMITTAL DATE: February 25, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Zoning cannot approve the building plans until all other PDSD review agencies have approved.

2. Development Package DP20-0211 must be approved before the building plans can be approved.

If you have any questions about this transmittal, please Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
03/16/2021 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed