Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM07421
Parcel: 133290060

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07421
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2020 JPEELDA1 FIRE REVIEW Approved
11/16/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the proposed plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2018
2. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Provide shower valves that comply with the requirements of Section 412.3 and 424.5, IPC 2018.
4. Show the location of the water heater serving the new bathroom. If the developed length of the hot water supply piping is greater than the maximum pipe length shown in Table C404.5.1, IECC, feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.
5. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Reference: Section 802.3, IPC 2018.
11/16/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code (e.g. COMcheck). Reference: Sections C103.2, C303, and C502.1, International Energy Conservation Code 2018.
2. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018.
3. Show how the new dough room is to be ventilated. Reference: Sections 401.2 and 401.3, IMC 2018.
11/16/2020 ROBERT SHERRY WATER REVIEW Completed
11/19/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/30/2020 SBLOOD1 ENGINEERING REVIEW Approved
12/01/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/01/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1.0; Plumbing Requirements: The occupant load has increased from 14 to 18. Per the IBC Section 2902.2(2), separate facilities for male/female occupants are not required when the total occupant load is 15 or less. Since the occupant load now exceeds 15, separate public facilities must be provided (one water closet and lavatory for males, one water closet and lavatory for females). Please verify.
2. Sheet T1.0; Building Height and Area: The Allowable Building Height (in feet) uses the IBC Table 504.3, the Allowable Building Height (in stories) uses the IBC Table 504.4, and the Allowable Building Area uses Table 506.2. Please revise those references on this sheet.
3. Sheet T1.0; Code Information: Please revise all code references on this sheet to correspond to the 2018 IBC.
4. Sheet A1.0; Floor Plan: In the area between the new Dough Room and the new Break Room, two Keynote references are incomplete. Please provide.
5. Sheet A1.0; Floor Plan: Please add a north arrow to the plan.
6. Sheet A1.0; Floor Plan: The West Wall Elevation is not indicated on the plan. Please verify.
7. Sheet S0.0; Structural Notes (General): Please verify where the 2000 PSF allowable soil bearing pressure was established.
8. Sheet S0.0; Structural Notes: Please add the structural notes for masonry.
9. Sheet S1.0; Plans: Please add north arrows to the plans.
10. General: Please provide structural calculations for the additions.
11. General: Please provide a Special Inspections Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
12. General: Please provide written responses to all review comments.
12/17/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: T20CM07421
8321 E Broadway Blvd.
TI Food Service
TRANSMITTAL DATE: December 17, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Zoning cannot approve the building plans until all other PDSD review agencies have approved.

2. Development Package DP20-0211 must be approved before the building plans can be approved.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package