Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM07345
Parcel: Unknown

Address:
2513 E 6TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM07345
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/08/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Second comment: Comment not addressed.] [Initial comment: Provide additional information from the roaster manufacturer regarding the vent for the coffee roaster: vent materials, positive or negative pressure venting, clearance from combustibles, chaff control, etc. Reference: Sections 301 and 304.1, IMC 2018.]
2. The additional information submitted on the proposed oven and the new chimney material does not resolve the issue. Submit an appeal to the building official to allow the use of a chimney instead of a Type I hood for the pizza oven. [Second comment: Comment not addressed. Section 507.2.2, IMC 2018 does not appear to allow for the use of anything but a Type I hood for wood-burning appliances.] [Initial comment: Provide additional information from the wood-fired pizza oven manufacturer regarding the installation and maintenance of a chimney to vent the oven. Reference: Sections 301 and 304.1, IMC 2018.]