Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM07345
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/20/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide additional information from the wood-fired pizza oven manufacturer regarding the installation and maintenance of a chimney to vent the oven. Reference: Sections 301 and 304.1, IMC 2018 |
01/20/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: The branch gas piping serving the existing AC unit (150 MBH @ 96 feet DL) is undersized, it should have a 1" supply. Reference: Section 402.1, IFGC 2018.] 2. Correct the total natural gas load note in the gas diagram to show 1099 MBH, not 1090 MBH. |
01/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |