Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM07345
Parcel: Unknown

Address:
2513 E 6TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM07345
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide additional information from the wood-fired pizza oven manufacturer regarding the installation and maintenance of a chimney to vent the oven. Reference: Sections 301 and 304.1, IMC 2018
01/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: The branch gas piping serving the existing AC unit (150 MBH @ 96 feet DL) is undersized, it should have a 1" supply. Reference: Section 402.1, IFGC 2018.]
2. Correct the total natural gas load note in the gas diagram to show 1099 MBH, not 1090 MBH.
01/26/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved